HVAC & AHU

Drives for HVAC pumps, fans and AHU.

Fan and pump curves are variable-torque loads, so the drive pays for itself on the cube law: at 80% speed a centrifugal fan draws roughly half the power. The G500 platform carries the loop control and the low-noise carrier setting.

Air handling unit fans and pumps driven by variable frequency drives
AHU fans and secondary pumps · variable torqueG500-G/P · 380 V

This duty at a glance

SeriesG500-G/P · G100 on small terminal units
Band0.75–710 kW
ControlV-F and sensorless vector · adjustable carrier
Overload150% / 60 s on the G rating

A frame number is only issued against the duty point: send the curve, the cycle or the belt data and the rating comes back confirmed, not estimated.

Platforms used for this duty

What this duty actually asks of the drive

Two numbers decide an HVAC drive: the acoustic noise in the occupied space and the energy at part load. Both are set in the same parameter — raise the carrier frequency and the motor runs quieter but the drive loses a few percent efficiency and heats up; lower it and the opposite happens.

The second requirement is that the drive must not fight the building management system. A 0–10 V or 4–20 mA demand signal, a run/fault contact and a Modbus register set are what the BMS integrator asks for first, and they are what the commissioning sheet is written against.

On a chiller or AHU fan the frame is taken at the motor rating because torque falls with the square of speed. The exception is a fan that has to start against a closed damper with a short ramp: that start is a loaded start and takes one frame up.

How the frame is chosen

Duty conditionFrame ruleWhat gets set
Centrifugal fan or secondary pumpP rating at motor kWCarrier raised for low audible noise in occupied space
Fan starting against a closed damperOne frame up on loaded startsRamp time extended, torque boost set
BMS-controlled AHUFrame at motor ratingDemand signal configured, fault and run contacts wired
Long cable run to a roof fanFrame unchangedCarrier reduced to 4 kHz or below

Frame numbers are issued against the duty point, not against the motor nameplate. Send the load profile — curve, head, cycle or belt data — and the rating is confirmed on it.

Where this platform stops

A page that claims to cover every case is worth less than one that says where the catalogue ends. These are the limits that decide whether the answer is a standard frame, a cabinet build, or a different platform entirely.

The published catalogue does not state a sound pressure level in dB(A) per frame — it is measured on the built unit, not quoted from this page.
BACnet is not listed as a built-in protocol in the published catalogue; RS-485 Modbus RTU is, on G600 and the servo series.
IP20 standard on the G500; roof and plant-room installations usually need the IP54 cabinet build, quoted separately.

Questions that come before a purchase order

Can the drive take a 0–10 V or 4–20 mA signal from the BMS?

Yes — the analog input is the standard speed reference and the run/fault relay contacts are wired to the BMS. Give the integrator the register map and the contact schedule from the manual and commissioning is a parameter load, not a programming job.

How much energy does a fan actually save at part speed?

On a variable-torque load the shaft power falls roughly with the cube of speed, so 80% speed is around half the power and 50% speed is around an eighth. The saving is real but it depends on the system curve and on how the damper or valve was previously doing the throttling — measure the existing duty before the payback is calculated.

Will the drive generate audible noise in the occupied space?

The carrier frequency is what is heard. Raising it moves the noise out of the sensitive band, at a small efficiency and heat cost. This site does not publish dB(A) figures per frame, so the value is measured on the built unit or confirmed on the sample.

Which platform for a small fan-coil or terminal unit?

The G100 micro drive covers 0.4–4 kW on 220 V single-phase with a front speed potentiometer and V-F control, which is the usual fit for small fans, circulating pumps and packaged units.

Other duty profiles

Next step

Send the duty point. Get a frame number back.

Power, voltage, load type and the number of units is enough to quote. Anything short of that gets a question back the same working day.