Size the duty, not the nameplate.
Enter the flow and the head. The page returns shaft power, the standard power band it snaps up to, and the platform that band belongs to — the three numbers a quotation cannot start without.
Duty point
Efficiency comes from the pump or fan curve at the duty point, not from the motor. A typical end-suction pump runs 55–75%; a backward-curved fan runs 60–75%.
What the numbers mean
| Term | How it is used |
|---|---|
| Shaft power | The power the pump or fan absorbs at the duty point, before any design margin. |
| Design margin | Headroom added on top of shaft power for fouling, cold starts and voltage sag. Ten percent is a normal starting point; abrasive slurry asks for more. |
| Standard power band | The next IEC size at or above the margined duty. Drives are not ordered in arbitrary sizes — they are ordered as a band. |
| Platform | The series that carries that band, and therefore the frame, the enclosure and the overload envelope you will be quoted. |
When this estimate is wrong
My pump nameplate says 11 kW but the calculator says 7.5 kW. Which wins?
The duty point wins. A nameplate is the maximum the motor can absorb; a pump that runs far left of its curve absorbs less. Size on the calculated shaft power plus margin, and keep the nameplate as the ceiling.
Does the margin cover a heavy start?
No — starting torque is an overload question, not a power question. A duty that starts against a closed valve or a full pipeline belongs on a platform with a 150% short-time overload rating, and the margin field will not tell you that.
What if the site is solar?
The power band is the same; the input stage changes. Solar pumping uses the MPPT variant in the same frame, so size the band here and specify the PV window separately.
Next
Take the band to the catalogue to see the frame and the package, or send the duty point and let the sales desk return a model code. Two routes, same answer.